Uni.FlyingStartStopTestOp merged with Uni.FlyingStartStopTestWithDivOp, IAdvancedControlBoard. ver. 3.1.1601
This commit is contained in:
@@ -10,33 +10,54 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
public class FlyingStartStopTestOp : IOperation
|
||||
{
|
||||
private static readonly ILog log = LogManager.GetLogger(typeof(FlyingStartStopTestOp));
|
||||
public override string ToString() { return string.Format("FlyingStartStopTestOp()"); }
|
||||
public override string ToString() { return string.Format("FlyingStartStopTestWithDivOp()"); }
|
||||
|
||||
/// Arguments of the constructor
|
||||
readonly UniCB uniCB;
|
||||
readonly TBF.Rig.Uni.RegValve.RegValve regV;
|
||||
readonly TBF.Rig.Uni.FlowMeter.FlowMeter flowMeter;
|
||||
readonly double qFrom;
|
||||
readonly double qTo;
|
||||
readonly int pulsesCount; /// Number of reference pulses for a complete test
|
||||
readonly int pulsesCount; /// Number of reference pulses for a complete test
|
||||
readonly bool withDiverter;
|
||||
readonly bool isProlonged;
|
||||
readonly int massPulsesCount; /// Number of reference pulses for mass collection
|
||||
readonly bool readDivTransition;
|
||||
readonly TBF.Rig.Uni.RegValve.RegValve regV;
|
||||
readonly TBF.Rig.Uni.FlowMeter.FlowMeter flowMeter;
|
||||
readonly int diverterNr;
|
||||
readonly int divThreshold;
|
||||
|
||||
/// <summary>
|
||||
/// Operation for a Flying start-stop test (constructor)
|
||||
/// Operation for a Flying start-stop test with a diverter (constructor)
|
||||
///
|
||||
/// Events: OpArgumentError .... invalid arguments, test cannot be started
|
||||
/// StartingTest ....... starting a test
|
||||
/// TestInProgress ..... test was successfully started, test is running
|
||||
/// TestCompleted ...... test was successfully completed
|
||||
/// Error .............. unspecified error while running a test
|
||||
/// Events: OpArgumentError ...... invalid arguments, test cannot be started
|
||||
/// StartingTest ......... starting a test
|
||||
/// TestInProgress ....... test was successfully started, test is running
|
||||
/// TestPart1InProgress .. test was successfully started, part1 of a prolonged test (collecting water) is running
|
||||
/// TestPart2InProgress .. first part of a prolonged test was successfully completed, part2 is in progress.
|
||||
/// Prolonged method only: (massPulsesCount GT 0) and (massPulsesCount LT pulsesCount)
|
||||
/// TestCompleted ........ test was successfully completed
|
||||
/// Error ................ unspecified error while running a test
|
||||
/// </summary>
|
||||
/// <param name="cb">Control board component</param>
|
||||
/// <param name="devices">Components used by the test</param>
|
||||
/// <param name="devices">Components used by the test</param>
|
||||
/// <param name="qFrom">Flow lower limit</param>
|
||||
/// <param name="qTo">Flow upper limit</param>
|
||||
/// <param name="pulsesCount">Test duration - number of reference flow meter pulses</param>
|
||||
public FlyingStartStopTestOp(UniCB cb, OutputPath devices, double qFrom, double qTo, int pulsesCount)
|
||||
/// <param name="withDiverter">true = Test with diverter</param>
|
||||
/// <param name="isProlonged">true = Prolonged test with diverter</param>
|
||||
/// <param name="massPulsesCount">Test part 1 duration - number of reference flow meter pulses<</param>
|
||||
/// <param name="readDivTransition">true = Read diverter transition</param>
|
||||
public FlyingStartStopTestOp(UniCB cb, OutputPath devices, double qFrom, double qTo, int pulsesCount,
|
||||
bool withDiverter, bool isProlonged, int massPulsesCount, bool readDivTransition)
|
||||
{
|
||||
this.uniCB = cb;
|
||||
this.qFrom = qFrom;
|
||||
this.qTo = qTo;
|
||||
this.pulsesCount = pulsesCount;
|
||||
this.withDiverter = withDiverter;
|
||||
this.isProlonged = withDiverter && isProlonged;
|
||||
this.massPulsesCount = massPulsesCount;
|
||||
this.readDivTransition = withDiverter && readDivTransition;
|
||||
|
||||
flowMeter = devices.FlowMeter as TBF.Rig.Uni.FlowMeter.FlowMeter;
|
||||
if (flowMeter == null) throw new ArgumentNullException("Invalid flow meter");
|
||||
@@ -44,18 +65,23 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
regV = devices.RegValve as TBF.Rig.Uni.RegValve.RegValve;
|
||||
if (regV == null) throw new ArgumentNullException("Invalid regulation valve");
|
||||
|
||||
this.qFrom = qFrom;
|
||||
this.qTo = qTo;
|
||||
this.pulsesCount = pulsesCount;
|
||||
diverterNr = (withDiverter && devices.Diverter is TBF.Rig.Uni.Diverter.Diverter)
|
||||
? (devices.Diverter as TBF.Rig.Uni.Diverter.Diverter).DiverterNr : 0;
|
||||
|
||||
divThreshold = (withDiverter && devices.Diverter is TBF.Rig.Uni.Diverter.Diverter)
|
||||
? (devices.Diverter as TBF.Rig.Uni.Diverter.Diverter).StartThreshold : 0;
|
||||
|
||||
log.Debug(this.ToString());
|
||||
}
|
||||
|
||||
/// Internal state of this operation
|
||||
/// Internal states of this operation
|
||||
enum OpState
|
||||
{
|
||||
StartingTest,
|
||||
ReadingDivTransition,
|
||||
TestInProgress,
|
||||
TestPart1InProgress, /// prolonged test only
|
||||
TestPart2InProgress, /// prolonged test only
|
||||
TestCompleted,
|
||||
}
|
||||
|
||||
@@ -66,10 +92,10 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
/// </summary>
|
||||
public void Start()
|
||||
{
|
||||
log.InfoFormat("Op.Start() RV#={0} Et#={1} Qfrom={2} Qto={3}", regV.Idx1, flowMeter.Idx1, qFrom, qTo);
|
||||
log.InfoFormat("Op.Start() RV#={0} Et#={1} Div#={2} Qfrom={3} Qto={4}", regV.Idx1, flowMeter.Idx1, diverterNr, qFrom, qTo);
|
||||
|
||||
/// Start the test (and the flow measurement)
|
||||
uniCB.StartTest(false, flowMeter.Idx1, 0, 0, true, false, false, false, pulsesCount, 0);
|
||||
uniCB.StartTest(false, flowMeter.Idx1, diverterNr, divThreshold, true, withDiverter, false, isProlonged, pulsesCount, massPulsesCount);
|
||||
|
||||
opState = OpState.StartingTest;
|
||||
}
|
||||
@@ -78,12 +104,15 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
/// Run this operation
|
||||
/// </summary>
|
||||
/// <returns>
|
||||
/// Event.OpArgumentError .... invalid arguments, test cannot be started
|
||||
/// Event.StartingTest ....... starting a test
|
||||
/// Event.TestInProgress ..... test was successfully started, test is running
|
||||
/// Event.TestCompleted ...... test was successfully completed
|
||||
/// Event.Error .............. unspecified error while running a test
|
||||
/// </returns>
|
||||
/// Event.OpArgumentError ...... invalid arguments, test cannot be started
|
||||
/// Event.StartingTest ......... starting a test
|
||||
/// Event.TestInProgress ....... test was successfully started, test is running
|
||||
/// Event.TestPart1InProgress .. test was successfully started, part1 of a prolonged test (collecting water) is running
|
||||
/// Event.TestPart2InProgress .. first part of a prolonged test was successfully completed, part2 is in progress.
|
||||
/// Prolonged method only: (massPulsesCount GT 0) and (massPulsesCount LT pulsesCount)
|
||||
/// Event.TestCompleted ........ test was successfully completed
|
||||
/// Event.Error ................ unspecified error while running a test
|
||||
/// </returns>
|
||||
public Event Run()
|
||||
{
|
||||
log.DebugFormat("Op.Run() opState={0}", opState);
|
||||
@@ -96,12 +125,16 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
{
|
||||
return Event.OpArgumentError; /// Invalid qFrom, qTo
|
||||
}
|
||||
if (isProlonged && (massPulsesCount <= 0 || massPulsesCount >= pulsesCount))
|
||||
{
|
||||
return Event.OpArgumentError; /// Invalid qFrom, qTo
|
||||
}
|
||||
|
||||
if (!flowMeter.MsrmntAvailable || /// Flow measurement not started yet
|
||||
(uniCB.State & (ulong)StatusP.ReadingCounters) == 0 || /// Test was not started yet
|
||||
uniCB.RefFrequency == 0) /// Measured flow is 0
|
||||
{
|
||||
return Event.StartingTest; /// Flow regulation cannot be started
|
||||
return Event.StartingTest; /// Flow regulation cannot be started
|
||||
}
|
||||
|
||||
/// Start flow regulation
|
||||
@@ -112,8 +145,17 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
uniCB.SetFlow(false, regV.Idx1, 2000 * reqFlowLo / flowMeter.NominalFlow,
|
||||
2000 * reqFlowHi / flowMeter.NominalFlow);
|
||||
|
||||
opState = OpState.TestInProgress;
|
||||
return Event.TestInProgress;
|
||||
opState = readDivTransition ? OpState.ReadingDivTransition
|
||||
: (isProlonged ? OpState.TestPart1InProgress : OpState.TestInProgress);
|
||||
|
||||
return isProlonged ? Event.TestPart1InProgress : Event.TestInProgress;
|
||||
|
||||
case OpState.ReadingDivTransition:
|
||||
|
||||
/// Read diverter transition data
|
||||
uniCB.ReadDiverterTransition(false, diverterNr);
|
||||
opState = isProlonged ? OpState.TestPart1InProgress : OpState.TestInProgress;
|
||||
return isProlonged ? Event.TestPart1InProgress : Event.TestInProgress;
|
||||
|
||||
case OpState.TestInProgress:
|
||||
|
||||
@@ -124,11 +166,30 @@ namespace TBF.Rig.ControlBoard.Uni
|
||||
opState = OpState.TestCompleted;
|
||||
return Event.TestCompleted;
|
||||
|
||||
case OpState.TestPart1InProgress:
|
||||
|
||||
if ((uniCB.State & (ulong)StatusP.DirectionOfDiverter) != 0)
|
||||
{
|
||||
return Event.TestPart1InProgress; /// Test was not completed yet
|
||||
}
|
||||
opState = OpState.TestPart2InProgress;
|
||||
return Event.TestPart2InProgress;
|
||||
|
||||
case OpState.TestPart2InProgress:
|
||||
|
||||
if ((uniCB.State & (ulong)StatusP.TestCompleted) == 0)
|
||||
{
|
||||
/// Test was not completed yet
|
||||
return Event.TestPart2InProgress;
|
||||
}
|
||||
opState = OpState.TestCompleted;
|
||||
return Event.TestCompleted;
|
||||
|
||||
case OpState.TestCompleted:
|
||||
default:
|
||||
return Event.TestCompleted;
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Stop this operation
|
||||
|
||||
Reference in New Issue
Block a user