Changes done on Fuzhou300 system:
- ControlComDev.SetFMFreq() modifications (array size) - StatusP and Route logging - StatusP bit assignments: bit3 -> bit5 - MettlerToledo logging
This commit is contained in:
@@ -9,6 +9,32 @@ namespace TBF.BenchControl.Elde
|
||||
Stop = 2, /// Stop the measurement
|
||||
}
|
||||
|
||||
#if FUZHOU300
|
||||
public enum StatusP : ulong
|
||||
{
|
||||
RefFlowMeterMask = 0x7,
|
||||
TestCompleted = 0x10,
|
||||
TestInProgress = 0x20,
|
||||
//DiverterError = 0x20,
|
||||
MsrmntWithDivrtr = 0x80,
|
||||
RefPulsesMsrmnt = 0x100,
|
||||
SynchroMethod = 0x800,
|
||||
WaterMeterCalib = 0x1000,
|
||||
EmgcyStopActive = 0x2000,
|
||||
MsrmntGateActive = 0x4000,
|
||||
TimeMeasurement = 0x8000,
|
||||
FrequencyMeasured = 0x80000,
|
||||
ADCError = 0x80000000,
|
||||
TimeoutOccured = 0x100000000,
|
||||
MeretAddresses = 0x200000000,
|
||||
SampleBuferFull = 0x400000000,
|
||||
ErrorTempMeter = 0x10000000000,
|
||||
ErrorPressMeter1 = 0x1000000000000,
|
||||
ErrorPressMeter2 = 0x2000000000000,
|
||||
ErrorPressMeter3 = 0x4000000000000,
|
||||
ErrorPressMeter4 = 0x8000000000000,
|
||||
}
|
||||
#else
|
||||
public enum StatusP : ulong
|
||||
{
|
||||
RefFlowMeterMask = 0x7,
|
||||
@@ -33,6 +59,7 @@ namespace TBF.BenchControl.Elde
|
||||
ErrorPressMeter3 = 0x4000000000000,
|
||||
ErrorPressMeter4 = 0x8000000000000,
|
||||
}
|
||||
#endif
|
||||
|
||||
public enum StopDevs
|
||||
{
|
||||
|
||||
@@ -114,11 +114,26 @@ namespace TBF.BenchControl.Elde
|
||||
int shortImp;
|
||||
StopDevs stopDevs;
|
||||
|
||||
/// <summary>
|
||||
/// Sets the power of the selected pump
|
||||
/// </summary>
|
||||
/// <param name="index">Pump index 0 .. 5, invalid pump index sets all pumps to 0%</param>
|
||||
/// <param name="power">Power (0.0f .. 100.0f)</param>
|
||||
public void SetFMFreq(int index, float power)
|
||||
{
|
||||
#if FUZHOU300
|
||||
if (index == 0) FMFreq = new float[6] { power, 0, 0, 0, 0, 0 };
|
||||
else if (index == 1) FMFreq = new float[6] { 0, power, 0, 0, 0, 0 };
|
||||
else if (index == 2) FMFreq = new float[6] { 0, 0, power, 0, 0, 0 };
|
||||
else if (index == 3) FMFreq = new float[6] { 0, 0, 0, power, 0, 0 };
|
||||
else if (index == 4) FMFreq = new float[6] { 0, 0, 0, 0, power, 0 };
|
||||
else if (index == 5) FMFreq = new float[6] { 0, 0, 0, 0, 0, power };
|
||||
else FMFreq = new float[6] { 0, 0, 0, 0, 0, 0 };
|
||||
#else
|
||||
if (index == 0) FMFreq = new float[2] { power, 0 };
|
||||
else if (index == 1) FMFreq = new float[2] { 0, power };
|
||||
else FMFreq = new float[2] { 0, 0 };
|
||||
#endif
|
||||
}
|
||||
|
||||
public void UpdateWeights()
|
||||
@@ -137,7 +152,7 @@ namespace TBF.BenchControl.Elde
|
||||
{
|
||||
if (cfg == null) throw new ArgumentNullException("cfg");
|
||||
this.controlBoardCfg = cfg;
|
||||
FMFreq = new float[2] { 0, 0 };
|
||||
FMFreq = new float[6] { 0, 0, 0, 0, 0, 0 }; /// Nr. of pumps: Fuzhou150=2, Fuzhou300=6
|
||||
emergencyStop = false;
|
||||
previousEmergencyStop = false;
|
||||
}
|
||||
|
||||
@@ -228,15 +228,22 @@ namespace TBF.BenchControl.Elde
|
||||
// regConst,
|
||||
// shortImp,
|
||||
// stopDevs));
|
||||
log.InfoFormat("SendCommand(Cmd={0}, Ref={1}, 0x{2}, Total={3}, TM={4}, filt={5}, FM=[{6},{7}], Reg={8}, ShrtImp={9}, Stop={10})",
|
||||
log.InfoFormat("SendCommand(Cmd={0}, Ref={1}, rt={2} {3} {4} {5}, Total={6}, TM={7}, filt={8}, FM=[{9},{10},{11},{12},{13},{14}], Reg={15}, ShrtImp={16}, Stop={17})",
|
||||
cmd,
|
||||
refFlowMeterNr,
|
||||
route.ToString("X"),
|
||||
((route >> 48) & 0xFFFF).ToString("X4"),
|
||||
((route >> 32) & 0xFFFF).ToString("X4"),
|
||||
((route >> 16) & 0xFFFF).ToString("X4"),
|
||||
(route & 0xFFFF).ToString("X4"),
|
||||
totalRefPulses,
|
||||
testMethods,
|
||||
filterConstant,
|
||||
fmFreq[0],
|
||||
fmFreq[1],
|
||||
fmFreq[2],
|
||||
fmFreq[3],
|
||||
fmFreq[4],
|
||||
fmFreq[5],
|
||||
regConst,
|
||||
shortImp,
|
||||
stopDevs);
|
||||
|
||||
@@ -55,8 +55,15 @@ namespace TBF.BenchControl.Elde
|
||||
public Event Run()
|
||||
{
|
||||
if (started) return Event.MeasurementStarted;
|
||||
if (0 != (controlBoard.StatusP & StatusP.TestInProgress))
|
||||
StatusP statusP = controlBoard.StatusP;
|
||||
log.DebugFormat("statusP = {0} {1} {2} {3}",
|
||||
(((ulong)statusP >> 48) & 0xFFFF).ToString("X4"),
|
||||
(((ulong)statusP >> 32) & 0xFFFF).ToString("X4"),
|
||||
(((ulong)statusP >> 16) & 0xFFFF).ToString("X4"),
|
||||
((ulong)statusP & 0xFFFF).ToString("X4"));
|
||||
if (0 != (statusP & StatusP.TestInProgress))
|
||||
{
|
||||
log.Info("Test started");
|
||||
started = true;
|
||||
return Event.MeasurementStarted;
|
||||
}
|
||||
|
||||
@@ -50,6 +50,7 @@ namespace TBF.BenchControl.MettlerToledo
|
||||
{
|
||||
result.Val = balanceDev.Mass;
|
||||
done = true;
|
||||
log.InfoFormat("ReadMassOp.Run() ... mass={0} ... returning Event.BalanceDone", balanceDev.Mass);
|
||||
balanceDev.GetImmediateMassMeasurement(); /// Start another measurement
|
||||
return Event.BalanceDone; /// Mass read OK
|
||||
}
|
||||
|
||||
@@ -72,6 +72,8 @@ namespace TBF.BenchControl.MettlerToledo
|
||||
for (int i = 1; i < totalReadingsCount - 1; i++) calcMass += massReadings[i];
|
||||
calcMass = (calcMass / (totalReadingsCount - 2));
|
||||
|
||||
log.InfoFormat("ReadStableMassOp.Run() ... valid mass={0} ... returning Event.BalanceDone", calcMass);
|
||||
|
||||
result.Val = calcMass;
|
||||
return Event.BalanceDone; /// Mass has just been calculated
|
||||
}
|
||||
|
||||
@@ -469,7 +469,7 @@ namespace TBF.BenchControl.Sequences
|
||||
///
|
||||
/// Stop the pump at the end of test
|
||||
///
|
||||
StateMachine.ControlBoard.SetFMFreq(0, 0); /// Stop FM controlled pumps
|
||||
StateMachine.ControlBoard.SetFMFreq(-1, 0); /// Stop FM controlled pumps
|
||||
State.Create("SequenceBase : Test(s) completed -> Stopping the pump")
|
||||
.AddOperation(checkUiOp)
|
||||
.AddOperation((inPath.Pump is GenericDevices.IPumpFM) ? (inPath.Pump as GenericDevices.IPumpFM).TurnOff() : null)
|
||||
|
||||
Reference in New Issue